Effects of inlet/outlet positions on the air cooling performance
The T
max, minimum temperature (T
min), ΔT, the pressure difference (ΔP: the difference between average inlet pressure and average outlet pressure) of each design at different inlet air velocities are collected every 100 s of the flow time from 0 to 3000s. The relationships between these four major parameters and inlet velocities are shown in
Figure 6. The general trends of all the designs were similar. As the airflow inlet velocity increases, the T
max, T
min and ΔT decrease while the ΔP increase.
At the inlet velocity of 1 m/s, all designs showed unsatisfactory performance in terms of T
max and ΔT. Design 0, Design 1 and Design 4 exhibited lower T
max among all the designs, which were 318.8 K, 317.87 K and 318.9 K, respectively. However, the ΔT of Design 0 and Design 1 were the highest among all the designs. At low inlet velocity (1 m/s), none of the designs met the requirement, but Design 4 still exhibited better overall cooling performances than other designs. The drawbacks of Design 0 and Design 1 were their uneven temperature distributions. From
Figure 7, although the T
max of Design 1 was the lowest one among all the designs, the ΔT between the cells near the inlet and the cells near the outlet reached more than 8 K. At low inlet velocity, the single inlet/outlet structure would cause significant ΔT, which was proportional to the distance between inlet and outlet.
When the inlet velocity reached 2 m/s, the T
max of Design 0, Design 1 and Design 4 and the ΔT of Design 3 and Design 4 met the requirements. Design 4 was the only design that met both the requirements. Design 0 showed the highest ΔT due to its longest distance between inlet and outlet. Design 1 showed a lower T
max (311.53 K) than Design 0 since its inlet to outlet distance was shorter than that of Design 0. For the same reason, the ΔT of Design 1 was smaller than Design 0. Shorter air-cooling channel length (inlet to outlet distance) was found to be beneficial to reduce both T
max and ΔT. The temperature distributions of Design 4 and Design 5 are shown in
Figure 8. The inlet and outlet areas of these two designs were the same, but the outlets of Design 5 were divided into four pieces on the left, right, top and bottom faces while the outlets of Design 4 were just two pieces equally divided on the top and bottom faces. The simulation results showed that both T
max and ΔT of Design 4 were lower than Design 5, especially the ΔT of Design 4 was 25% lower than that of Design 5. More outlet quantity does not necessarily mean better cooling performances. If the outlet positions were not suitable, it would adversely release unheated air before the sufficient heat exchange processes between air and cells, causing larger T
max and ΔT.
In the scenario of 3 m/s inlet velocity, the T
max of six designs were all lower than 313.15 K, but the Design 0 and Design 2's ΔT were higher than 5 K. From the comparison of the temperature distributions of Design 1 at 1 m/s and 3 m/s, the temperature uniformity improved obviously as the inlet velocity increased. The high ΔT between the cells near the inlet and the outlet disappeared probably due to three reasons: (1) the fast inlet airflow did not carry as much heat from the cells close to the inlet as it did when the airflow velocity was lower, that is, not enough time for heat exchange; (2) there was sufficient unheated airflow at the end of the cooling channel to cool down the cells close to the outlet; (3) the synergy angle between the direction of the temperature gradient field and the direction of the velocity field became 0 (both were from the inlet to the outlet), which meant the highest heat transfer efficiency was achieved. As a result, the temperature uniformity improved significantly when the inlet velocity reached 3 m/s. In
Figure 6(c), all designs exhibited temperature uniformity improvements from 1 m/s to 2 m/s as well as from 2 m/s to 3 m/s. Only the ΔT of Design 2 increased from 2 m/s to 3 m/s. The reason was that its T
min decreased a lot from 2 m/s to 3 m/s in
Figure 6(b), causing a larger ΔT contrarily. In conclusion, reducing the battery T
max is not the only objective of a good air-cooling system, a well-designed BTMS should also deliver excellent temperature uniformity. Both hot and cold spots should be avoided to obtain a satisfactory temperature uniformity.
At 4 m/s airflow inlet velocity, although T
max and T
min in all designs kept decreasing, the ΔT improvements of Design 1, Design 2, Design 3 and Design 4 were almost neglectable or even backwards. In
Figure 6(a) and (b), the slopes of both T
max and T
min increased slightly, which meant the cooling effect improvements due to the increase of the inlet velocity are going down. Presumably, increasing the inlet velocity could reduce system temperature, but the cooling effect improvement from 3 m/s to 4 m/s was not as good as that from 1 m/s to 2 m/s. There would be some thresholds of the cooling performance improvements as the inlet velocity was continuously increasing because the temperature of the inlet air was fixed. The smaller the gap between inlet air temperature and battery cells temperature is, the lower cooling efficiency the system will deliver. The battery cells will never be cooled down below the inlet air temperature.
The overall thermal performances at 5 m/s were similar to those at 4 m/s. The ΔT of Design 2 was still larger than 5 K. The temperature and airflow velocity distributions of Design 2 was shown in
Figure 9. The hot spots usually occurred in the places where airflow velocities were relatively low. The stagnant air flows diminished the heat convection and conduction processes between cells and air. Designers should optimize the cooling channels to avoid low-velocity spots. Design 0 offered the lowest T
max at 5 m/s while its T
max was higher than Design 1 at 1 m/s. When the airflow is sufficient (inlet velocity is high), the longer cooling channel could provide better cooling performance to reduce T
max. On the other hand, the ΔP of Design 0 was the highest among all designs. Due to the viscous loss, high-pressure difference between outlet and inlet means high energy loss, indicating the energy consumption of the active air-cooling system is high. Design 2 and Design 3 delivered very close pressure difference values due to their similar inlets and outlets positions as well as their BTMS layouts. And so did Design 4 and Design 5. Generally, ΔP is relevant to the layout of the BTMS designs, including the inlet and outlet positions, numbers, sizes, as well as cooling channel distributions.
In conclusion, a good air-cooling BTMS design should be able to reduce Tmax as much as possible and keep Tmin sticking to Tmax to achieve a minimum ΔT. Both hot spots and cold spots shall be avoided in a well-designed air-cooling BTMS. Second, the effects of cooling performance improvement by increasing the inlet velocities are more apparent in reducing the temperatures (Tmax and Tmin) than the ΔTs. Higher inlet velocity means more energy consumption, if the requirement (Tmax ≤ 313.15 K and ΔT ≤ 5 K) is already met, it is not economic to further increase the inlet velocities because the extra energy consumption will compromise the overall driving ranges. From the simulation results and the above analysis, only Design 4 could meet all requirements when the inlet velocity was 2 m/s. Even at 3 m/s inlet velocity, its cooling performance was still among the top designs. At 2 m/s inlet velocity, the Tmax of Design 4 was 313.05 K and its ΔT was 2.24 K (35.5%) lower than the basic design 0 with a minimum ΔP of 1.92 Pa among Designs 0–5. So, Design 4 is the optimal air-cooling BTMS design among all six designs in this study.
The effects of outlet dimensions on the cooling performance
To investigate the relationship between outlet dimensions and cooling effects, this study proposed four derivative designs with different outlet widths (W) based on the optimal Design 4 in
Supplementary Table 5.
The outlet widths (W) of Designs 6, 7, 8, 9 and 4 (0.01 m, 0.02 m, 0.03 m, 0.04 m and 0.05 m) were shown in
Figure 10. Except for the outlet dimensions, all other parts were identical. Simulations were carried out under the same operating conditions to evaluate the influence of the outlet widths on the cooling effects.
Supplementary Figure 11 showed the simulation results of the air-cooling BTMS with five different outlet dimensions. Generally, the differences between T
max and T
min of five designs at different inlet velocities were not large, but ΔT showed some obvious divergences when the inlet velocity was higher than 2 m/s. Lower T
max and higher T
min are beneficial to the temperature uniformity. Coincidentally, the 0.02 m design exhibited the most numbers of lowest T
max (three times), highest T
min (three times) and lowest ΔT (three times). It delivered optimal cooling performances with both the lowest T
max and ΔT when the inlet velocities were 3 m/s, 4 m/s and 5 m/s. After the inlet velocity reached 2 m/s, all 5 designs had met the requirements (T
max ≤ 313.15 K and ΔT ≤ 5 K). At 2 m/s, the 0.03 m design showed both the lowest T
max and ΔT. Compared with the original 0.05 m Design 4, 0.03 m design provided a 0.47 K reduction in T
max and a 0.28 K reduction in ΔT with a minor 15.61 Pa ΔP increase. On the other hand, ΔP of the smaller outlet width designs were exponentially higher than larger ones as shown in
Supplementary Figure12. ΔP of 0.01 m design was over 10 times higher than 0.05 m design at all five inlet velocities, indicating significantly higher energy consumptions of smaller outlet dimensions. ΔP of 0.03 m design was only about half of 0.02 m design, showing a major benefit of saving the energy consumption.
As a result, Design 4 with 0.03 m outlet and a 2 m/s inlet velocity was considered an optimal combination of both lowest Tmax (312.58 K) and ΔT (3.79 K) in addition to a reasonable energy consumption level (14.9 Pa). Compared with the worst case of 0.05 m design (Tmax = 313.05 K, ΔT = 4.07 K), Tmax and ΔT had been improved by 0.15% and 6.88%, respectively.
The optimal design with different discharging rates, ambient temperatures and inlet airflow velocities
To give a detailed understanding of the real working conditions of the EV battery pack and investigate the cooling performances of the air-cooling BTMS during these operations, different ambient temperatures, discharge rates and inlet air velocities should all be considered. In this section, the optimal design would be tested with more than 52 groups of new simulations with different discharging rates (0.5–1.5C), ambient temperatures (10–30°C) and inlet airflow velocities (0.2–14 m/s) to check its practicality in real application scenarios and efficiency under various operating conditions. Theoretically, the average discharging rate of an EV is about 0.1C, which could provide a continuous 10-hour operating time to cover a 500 km milage with a speed of 50 km/h. The 1.5C could already be considered as the higher discharging rate since it is 15 times of the theoretical average discharging rate. The 3–5C or higher C-rate could be implemented in the fast charging and abusive driving scenarios, which could be further explored in some specialized research by more advanced cooling methods while the pure air-cooling BTMS could hardly handle. By the definition from Li et al.,
32 fast charge has been coined for charging rates of about 4C (i.e. a theoretical 15-minute charge) but less than 6C (i.e. a theoretical 10-minute charge). So, the discharging rates of 0.5–1.5C were specially investigated in this part.
The simulation results were shown in
Supplementary Figure 13. Generally, the differences between T
max and T
min at different ambient temperatures were almost equivalent to the differences of the ambient temperatures in the same operating conditions. Theoretically, since T
max and T
min were simultaneously affected by the ambient temperatures, ΔT was almost not influenced by different ambient temperatures. Moreover, ΔP was mainly resulted from the frictional and viscous losses within the cooling channels and dominated by inlet velocity, cooling channel structure, inlet/outlet dimensions, etc. So, in
Supplementary Figure 13, the ambient temperatures were not considered a relevant factor in the relationship between ΔT/ΔP and inlet velocities. Instead, the discharging rate was chosen as the main operating condition to assort the simulation results as shown on the right part of
Supplementary Figure 13.
During 0.5C discharging (2 A discharging current), the cooling effect of the optimal design was satisfactory that even lower inlet velocities (0.4 m/s) could meet the temperature requirement. At 283.15 K, the inlet velocity of 0.4 m/s could deliver a required cooling performance with a Tmax of 296.51 K and a ΔT of 3.77 K. When the inlet velocity was increased to 5 m/s, Tmax and ΔT were reduced to 288.47 K and 1.53 K, respectively. The cooling performance at 293.15 K was the same as that at 283.15 K, so a 0.4 m/s inlet airflow was sufficient. At 303.15 K, the minimum inlet velocity meeting the temperature requirement rose to 0.8 m/s. Tmax and ΔT at 0.8 m/s inlet velocity during 0.5C discharging were 312.93 K and 2.18 K, respectively.
During 1C discharging (4 A discharging current), the cooling effect of the optimal design is reduced with the increase in heat generation. When the ambient temperature was 283.15 K, 2 m/s inlet velocity was sufficient to deliver the required cooling performance with Tmax and ΔT of 302.97 K and 4.36 K, respectively. The cooling performance could be enhanced to Tmax (296.35 K) and ΔT (3.88 K) when the inlet velocity was increased to 5 m/s. Similarly, 2 m/s was also the minimum inlet velocity for the design to deliver qualified thermal performance when the ambient temperature is 293.15 K. At 303.15 K, none of the inlet velocities from 1 m/s to 5 m/s could maintain the Tmax below 313.15 K despite the ΔT could still be effectively controlled within 5 K when the inlet velocity was greater than 2 m/s. The lowest Tmax (316.35 K) could be achieved when the inlet velocity was 5 m/s. The limitation of the air-cooling method started to be exposed when the ambient temperature (inlet air temperature) was close to the upper limit of the ideal temperature range (313.75 K), which was also a challenge to all cooling methods that the cooling performances could greatly compromise when the margin between coolant and threshold was relatively small.
During 1.5C discharging (6 A discharging current), none of the cooling performances at all three ambient temperatures was satisfied due to high ΔT. At 283.15 K, 8 m/s inlet velocity could deliver a required Tmax of 304.97 K, but the ΔT was 7.44 K. Even if the inlet velocity was increased to 14 m/s, the ΔT was still 5.76 K, which was 15.2% higher than the 5 K requirement. At 293.15 K, 11 m/s could keep the Tmax below 313.15 K, but its ΔT was still 1.29 K higher than 5 K. When the ambient temperature was 303.15 K, 14 m/s inlet velocity could not provide the required cooling performance. Its Tmax (317.58 K) was 3.83 K higher than 313.15 K and its ΔT (5.76 K) was 0.76 K higher than 5 K. Under the severe operating conditions of both high ambient temperature and discharging rate, the optimal air-cooling BTMS design could not provide the required temperature range for the battery pack.
Basically, if the average operation hours of a fully charged EV battery pack from 100% SoC to 0% SoC is 10 h, the average discharging rate of the battery pack is presumably to be 0.1C, which is around 10 times lower than the simulation discharging rates in this study. The additional simulation results in this section exhibited the superb cooling performances of the optimal design during mild and above-average EV working conditions (0.5C and 1C discharging operations), especially the air-cooling process during 0.5C discharging at 0.4 m/s inlet velocity was an effective energy-saving strategy for the EV BTMS. The air-cooling strategy of 2 m/s inlet velocity during 1C discharging was also effective for most of the working conditions. Nonetheless, a perfect BTMS is supposed to be able to tackle extreme working conditions. The 1.5C discharging rate could be considered as abusive driving condition since it is 15 times higher than the EV theoretical discharging rate. The air-cooling BTMS design in this study could hardly tackle this working condition even though the inlet velocity was increased to 14 m/s. If abusive discharging is unavoidable, the maximum inlet velocity is 14 m/s, and the ambient temperature is 303.15 K (30°C), the only adjustable variant is the inlet air temperature. Auxiliary inlet air pre-processing methods such as air conditioning or thermoelectric cooler should be introduced to achieve the desired cooling performance of the air-cooling BTMS during extreme working conditions.